Maximum demand charges and a factory battery: what to check

A battery that charges at the wrong moment can add to your recorded maximum demand. How MD is measured and billed, what time of day tariffs change, and why twelve months of bills come before any figure.

Vyut guide · updated 14 October 2026

A battery beside the genset saves diesel by carrying the plant through short power cuts. Afterwards it has to be recharged from the grid, and that recharge is load like any other. Charge it at the wrong moment and it can add to the one number on your electricity bill that is set by your single busiest half hour of the month: maximum demand.

This is one of the easiest ways for a battery project to give back part of what it saves, and one of the easiest to avoid, provided someone reads your electricity bills before any figure is put in writing.

What is maximum demand, and how is it billed?

Your meter does not only count units. It also records the highest average load you drew over a short, fixed interval during the billing cycle. Delhi's DERC Supply Code and Performance Standards Regulations, 2017 are a clear example. They define maximum demand as the highest average load, in kVA or kW at the point of supply, during a consecutive period of thirty minutes (or another period the Commission notifies) in a billing cycle. They define billing demand as the higher of your contract demand and the maximum demand the meter recorded.

Under rules like these, the demand charge on your bill, a rate in rupees per kVA or kW each month, is paid on whichever is higher. Run one half hour above your contract demand and the whole month is billed at that figure, and your state's tariff order may add more for exceeding contract demand. Check your own tariff schedule: the Electricity (Rights of Consumers) Amendment Rules, 2023 require every distribution licensee to display the tariff for each category of consumer on its website.

Smart meters add a rule of their own. Under the same 2023 amendment, if a smart meter records maximum demand above your sanctioned load in a month, that month's bill is calculated on the actual recorded demand. If it happens at least three times in a financial year, the lowest of those monthly readings becomes your revised sanctioned load from the next financial year. A habit of brief overshoots can raise your sanctioned load, and the charges that go with it, from the next year.

How could a battery raise my maximum demand?

By charging during the half hour when the plant is already at its busiest. The riskiest moment is easy to picture: the grid comes back after a cut, every machine restarts, and the battery, which has just carried the plant, starts to recharge at the same time. If both happen inside the same thirty-minute window, their loads add.

Illustrative round numbers, not from a real site. A plant has a contract demand of 900 kVA and its highest half hour in a normal month reads 800 kVA. Its battery can charge at up to 500 kW. If the battery recharges at full rate during that busy half hour, recorded demand jumps well past 900, and the month is billed on the higher figure, plus whatever your tariff order charges for the excess. That is how a battery can quietly give back part of what it saves.

How is that avoided?

If your tariff structure makes charging outside the peak window impossible, the economics change, and we tell you so with your electricity bill in hand rather than after the system is installed.

How do time of day tariffs change the picture?

Time of day tariffs price energy by the hour as well as demand by the month. Under the same 2023 amendment to the Rights of Consumers Rules:

For a battery this cuts both ways. Recharging in solar hours or normal hours costs less per unit than recharging in the peak, so the charging plan should favour them. But power cuts do not wait for cheap hours: a cut that ends at the start of the evening peak leaves a choice between recharging at the peak rate or waiting. Your state sets its own slots and rates, so read your tariff order rather than assuming another state's.

Two things we deliberately leave out of every saving we show: time of day arbitrage (charging cheap and discharging dear) and demand charge shaving. The battery's cycles are there to carry your power cuts. Our savings case values each stored unit at your landed grid tariff, the whole bill divided by the units billed, as our guide to what a unit from your DG set really costs explains.

What should I pull from twelve months of bills?

Twelve months, because maximum demand moves with the seasons and with production. From each bill, note:

Item on the billWhy it matters
Contract demand or sanctioned loadThe ceiling the battery's charging must stay under
Recorded maximum demand each monthThe headroom: contract demand less the highest month
Billing demand and demand charge rateWhat one bad half hour would cost
Any excess demand or penalty lineWhether exceeding contract demand already happens
Time of day slots and rates, if shownWhen recharging is cheapest and dearest
Total bill and units billedYour landed tariff, the cost of each stored unit

If your meter or DISCOM portal shows the date and time of each month's maximum demand, note that too: it tells you when the plant is busiest, which is when the battery should not be charging hard.

What if there is little or no headroom?

Then there are three honest options, and we would rather discuss them before anything is signed:

  1. Charge more slowly, for longer, at hours when the plant is quiet, and accept that a pack may not be full when cuts come close together.
  2. Raise your contract demand. This is a formal application to your DISCOM with its own costs. In Delhi, for example, the supply code describes an increase in sanctioned load or contract demand together with an enhanced security deposit and, where the service line changes, further charges.
  3. Change the sizing, so the battery's charging power fits inside the headroom you have.

If none of these works for your plant, the battery case is weaker than the diesel numbers alone suggest, and you should hear that from us early. A battery that saves diesel and gives it back in demand charges is not a saving.

The other side of the case is how often your power fails. A battery earns only when it is used, and your DG controller has been counting your cuts for years; our guide to reading the start counter and engine hours shows where to look. For why the battery takes only the short cuts and leaves the long ones to the genset, read battery storage vs a diesel generator. The genset stays: what we build is a backup to your genset, not a replacement for it.

Bring the bills, we will do the arithmetic

Our savings calculator takes your diesel spend, your power cut pattern and your landed grid tariff, shows the full working, and says plainly when it advises against going further. For the demand side, send us twelve months of electricity bills with the free ten-minute read of your DG panel, and we will show you the headroom and the charging plan before any proposal. Call or WhatsApp +91 8920 110 530, or write to contact@vyut.in. More answers are on our FAQ.

What would it save your plant?

The savings calculator runs on your diesel spend and your belt's diesel price and shows the full working, including when the answer is no.

More guides

Battery energy storage for factories in India: a plain guideWhat a commercial and industrial battery is, how long it lasts, how it takes over when the grid fails, how it should be sized, what the CEA's new safety rules require, and how buying one works.Battery storage vs diesel generator: why a factory needs bothA battery is instant and costs far less per unit. A genset runs for as long as there is fuel. For most factories the right answer is the battery for short cuts and the genset for long ones.What does a unit from your DG set really cost?About ₹27.70 a kWh at our reference plant, against ₹10 for grid power. Here is the arithmetic behind that figure and how to work out your own from litres and kWh.How to read your DG set's start counter and engine hoursTwo numbers on your generator's controller tell you how often your power fails and how long it stays off. Here is where to find them, the arithmetic, and the corrections that keep it honest.