Two numbers on your generator's controller tell you how often your power fails and how long it stays off. Here is where to find them, the arithmetic, and the corrections that keep it honest.

Vyut guide · updated 11 October 2026

Every modern DG controller keeps two running totals that almost nobody reads: the number of times the engine has started, and the number of hours it has run. Together they answer the two questions that decide what a power cut is costing your plant: how often does the grid fail, and how long does it stay off?

They beat every other source. Your DISCOM's reliability figures are averages over a whole licence area, usually leave out short interruptions, and many DISCOMs publish none at all. Memory is worse. The controller has been counting, quietly and without bias, since the day it was fitted.

Why are these two numbers worth ten minutes?

Because frequency and duration, not the size of the diesel bill, decide what can be done about it. Two plants with identical fuel bills can be in completely different positions: one burns its diesel in hundreds of short cuts, the other in a few long ones. Loading the set better, trimming load, a dual fuel kit or a battery for the short cuts each suit a different pattern. Our guide on reducing diesel generator cost covers which suits which.

The start counter also gives you something no fuel invoice can: a dated, physical record you can put in front of your DISCOM engineer.

Where do I find starts and engine hours on my controller?

Menus differ by model and firmware, so the most reliable method is not to hunt. Press the page or scroll button through the entire loop of instrument screens and photograph every one. Then look through the photos at your desk. Here is where the numbers usually live:

Controller familyWhere to lookNotes
Deep Sea Electronics (DSE), for example the 6110, 7320 and 8610 familiesThe accumulated instrumentation pages, reached by scrolling through the instrument pages: engine hours run, number of starts, and kWh on many modelsVery common on Indian industrial sets. DSE documents that accumulated values reset when they pass their maximum, so a suspiciously low count on an old set may be a rollover rather than a young controller.
ComAp InteliLite and InteliGenThe Statistics group: run hours, number of starts, unsuccessful starts, kWhShows unsuccessful starts as a separate figure, which saves you one of the corrections below.
Cummins PowerCommand, for example PCC 1302, 2100 and 3300The operator panel's history or status menus: engine starts and engine run timeMenu names vary with the operator panel fitted; photograph each history screen.
Other electronic controllersA menu called statistics, history, counters or accumulated valuesThe manual for your model names it. Photograph the whole loop anyway.
Plain AMF panel with a mechanical hour meterHours onlyNo start count. See the section on panels without a counter below.

While you are at the set, also photograph the DG nameplate (kVA rating, engine make, year of manufacture) and the AMF or mains failure logbook if one is kept at the panel.

What do the two numbers tell me?

Once the corrections in the next section are made:

Both are "roughly" for a good reason. A cut shorter than the controller's start delay never starts the engine, so it never reaches the counter. Those very short dips can still trip machines, but they burn no diesel, and for a diesel question the counter is measuring exactly what matters. The average also hides the spread: an average of 75 minutes can be many 20 minute cuts and a few four hour ones. The AMF logbook, if you keep one, shows the spread.

Which corrections make the count honest?

The counter counts engine starts, not power cuts, and the two are not the same. Make these corrections before believing the result:

  1. When was this controller fitted? This is the most important question of all. The counter belongs to the controller, not the engine. A panel replaced in 2023 on a 2016 set shows three years of starts, not ten. Divide by the wrong number of years and your answer can be out by a factor of three. If nobody remembers, the cross-checks below will tell you.
  2. Take out test runs. Most plants exercise the set on a schedule, often weekly and often for around ten minutes. A weekly test adds 52 starts a year that are not power cuts. Ask what the regime is and subtract both the starts and the hours.
  3. Take out failed starts. A start that fails and is retried counts twice for one cut. ComAp shows unsuccessful starts separately; on other controllers, check the event log or ask the engineer how often the set fails to start first time.
  4. Take out manual starts. Runs for servicing, load tests or commissioning work are not power cuts.
  5. Read every set. On a site with two or more sets on a lead and lag or synchronising arrangement, starts are split between the panels. Read all of them, or you will count half your cuts.
  6. Watch for rollover. An old set showing very few hours or starts has probably had a new controller, or a counter that has reset. Ask again.

A worked example

Illustrative numbers, not from a real site. A 500 kVA set with an electronic controller shows:

ReadingValue
Number of starts1,900
Unsuccessful starts40
Engine hours2,150 h
Controller fitted3 years ago
Test regimeWeekly, about 10 minutes: 156 starts and 26 hours over 3 years
Service runsAbout 8 a year, half an hour each: 24 starts and 12 hours

Those two figures, with your diesel invoices and your landed grid tariff, are what any serious assessment of the site should start from. Whether a pattern like this one makes a battery worthwhile depends on the rest of those numbers too, which is exactly what our calculator works out.

How do I check the result against my fuel bill?

The panel and your fuel invoices are independent records, so they should tell the same story. If they disagree, one of them is wrong. From the example:

If the invoices say about ₹3.6 lakh a month, panel and fuel agree and both are trustworthy. If they say twice that, the counter is probably under-counting (a controller swap nobody remembered is the usual cause) or the set is carrying load outside power cuts. If they say half, the counter may have rolled over or the test runs are longer than stated. A gap of more than about a quarter is a reason to stop and find out why, not a rounding difference. Our guide on what a unit from a DG set costs explains the litres per kWh figure and how load changes it.

A second quick check: engine hours against the age of the set. A ten-year-old set showing a few hundred hours has almost certainly had a new controller.

What if my panel has no start counter?

An old AMF panel with a mechanical hour meter records hours but not starts. Two fallbacks:

Get it read free, or run the numbers yourself

We will read your DG controller for you: start counter, engine hours, the corrections above and the fuel cross-check. It takes about ten minutes at the panel with your maintenance engineer, it costs nothing, and you keep the data whether or not you ever buy anything from us. Ginti free mein, das minute mein, data aapka. Call or WhatsApp +91 8920 110 530, or write to contact@vyut.in.

If you already have your readings, the power cuts step of our savings calculator takes lifetime starts and years directly and turns them into cuts per year. To see why the average cut length matters for sizing a battery, read battery storage vs a diesel generator. More answers are on our FAQ.

What would it save your plant?

The savings calculator runs on your diesel spend and your belt's diesel price and shows the full working, including when the answer is no.

More guides

Battery energy storage for factories in India: a plain guideWhat a commercial and industrial battery is, how long it lasts, how it takes over when the grid fails, how it should be sized, what the CEA's new safety rules require, and how buying one works.Battery storage vs diesel generator: why a factory needs bothA battery is instant and costs far less per unit. A genset runs for as long as there is fuel. For most factories the right answer is the battery for short cuts and the genset for long ones.What does a unit from your DG set really cost?About ₹27.70 a kWh at our reference plant, against ₹10 for grid power. Here is the arithmetic behind that figure and how to work out your own from litres and kWh.GRAP and diesel generators in Delhi NCR: what the rules say nowChecked against CAQM's own documents on 11 October 2026. DG rules now sit in GRAP Stage I, compliant sets carry no daily hour limit, and older sets need dual fuel or a certified emission control device, depending on size.